{"id":12120,"date":"2026-11-17T21:33:05","date_gmt":"2026-11-17T18:33:05","guid":{"rendered":"https:\/\/risys.sa\/?post_type=product&#038;p=12120"},"modified":"2026-11-17T21:33:05","modified_gmt":"2026-11-17T18:33:05","slug":"apc-ap9559-basic-rack-pdu","status":"publish","type":"product","link":"https:\/\/risys.sa\/en\/product\/apc-ap9559-basic-rack-pdu\/","title":{"rendered":"APC AP9559 Basic Rack PDU 1U, 16A C20, 120\/208\/230V"},"content":{"rendered":"<p>The APC AP9559 is the multi-voltage member of this rack PDU family. It accepts a 16 A input through an IEC 60320 C20 connector and runs on 120 V, 208 V or 230 V, so the same strip can serve a cabinet whichever of those supplies the building provides. It is a basic 1U unit that mounts horizontally at the front or rear of the rack and distributes up to 3680 VA across 10 IEC 60320 C13 outlets and 2 IEC 60320 C19 outlets. That outlet mix covers the typical small and mid-size cabinet: switches, routers, servers and recorders on C13, with the two C19 sockets kept for the equipment that draws more. There is no circuit breaker on the unit and no load metering, which keeps the strip simple and leaves overcurrent protection to the distribution board that feeds it.<\/p>\n<h2>How the APC AP9559 works in practice<\/h2>\n<p>A basic PDU does one job: it takes a single feed and turns it into a row of outlets inside the rack. The AP9559 does that from a 16 A input, and because the input is a standard IEC 60320 C20 connector rather than a hard-wired joint, the strip is easy to disconnect, move or replace. The cable runs 2.49 m, enough to reach a supply point beside or beneath the cabinet without an extension lead.<\/p>\n<p>A load capacity of 3680 VA sizes the strip for a moderately loaded cabinet rather than a dense one. The C13 outlets suit the standard IEC power cords supplied with switches, firewalls and many servers, while the C19 outlets suit higher-current equipment such as larger servers and storage enclosures. Since the unit has no on-board breaker, protection sits upstream: an overload or a fault in a connected device trips the breaker in the distribution board feeding the strip, so that breaker should be chosen to match the 16 A input.<\/p>\n<p>Horizontal mounting at the front or rear gives the installer a choice. At the rear, the outlets sit close to the power inlets of most devices and cords stay short; at the front, they are easier to reach in open racks or when a device needs to be unplugged quickly during maintenance.<\/p>\n<h2>APC AP9559 use cases across Saudi sectors<\/h2>\n<p>Bank branches and retail chains across the Kingdom typically run one network cabinet per site, and that is where the AP9559 fits: powering the router, the switches and a small server from a single circuit. Schools and clinics with a compact IT room benefit from the same simplicity, since a basic strip needs no setup before use. On CCTV projects, one AP9559 can feed a rack holding NVRs and PoE switches, keeping power distribution tidy and easy to trace during maintenance.<\/p>\n<p>The voltage range helps contractors who work across buildings wired differently. A single model that runs on 120 V, 208 V or 230 V means one strip to stock and specify across sites, rather than a different part for each. Edge network rooms at telecom and internet providers, and server closets in government buildings, gain the same advantage when they standardise spare parts between locations.<\/p>\n<p>The unit is rated to operate from 0 to 45 \u00b0C. In a Saudi summer that upper limit is a real constraint: the strip belongs in an air-conditioned server room or a cooled cabinet, not in an unventilated enclosure on a rooftop or in a car park.<\/p>\n<h2>The AP9559 against its siblings<\/h2>\n<p>Within the family, what sets the AP9559 apart is its flexibility on voltage and its mixed outlet layout. The closest alternative is the AP9565, rated 3.7 kW at 230V 16A or 3.3 kW at 208V 16A, but its outlets are all C13, so it suits cabinets without high-current devices. The AP8886, a 32 A metered strip, moves into a different class altogether: three-phase supply, vertical mounting and far more outlets, aimed at dense data centre racks.<\/p>\n<p>Choose the AP9559 when you have a single 16 A feed, a total load that stays within 3680 VA, a need for both C13 and C19 outlets, 1U of horizontal space free in the rack, and no requirement to read the load at the rack itself.<\/p>\n<h2>Deployment notes<\/h2>\n<p>Reserve 1U at the front or rear of the rack, fix the strip with the rack mounting brackets supplied in the box, and read the user manual before starting. The input connector is IEC 60320 C20, so the supply point needs a matching IEC 60320 C19 receptacle. Confirm the circuit voltage before connecting, and make sure the distribution board breaker suits a 16 A circuit, because the unit has no breaker of its own. Add up the load of the connected devices so it stays below 3680 VA with a safety margin, especially since the strip shows no load reading. The unit carries a 24-month warranty.<\/p>\n<h2>Package Contents<\/h2>\n<ul>\n<li>Rack PDU unit<\/li>\n<li>User manual<\/li>\n<li>Rack mounting brackets<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>A basic 1U rack PDU that runs on 120 V, 208 V or 230 V from a 16 A IEC 60320 C20 input and distributes up to 3680 VA across 10 C13 and 2 C19 outlets.<\/p>\n","protected":false},"featured_media":21050,"comment_status":"open","ping_status":"closed","template":"","meta":{"_acf_changed":false},"product_brand":[716],"product_cat":[851],"product_tag":[],"class_list":["post-12120","product","type-product","status-publish","has-post-thumbnail","product_brand-apc","product_cat-power-distribution-pdu","first","onbackorder","sale","taxable","shipping-taxable","purchasable","product-type-simple"],"acf":[],"_links":{"self":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12120","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/comments?post=12120"}],"version-history":[{"count":1,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12120\/revisions"}],"predecessor-version":[{"id":12121,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12120\/revisions\/12121"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media\/21050"}],"wp:attachment":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media?parent=12120"}],"wp:term":[{"taxonomy":"product_brand","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_brand?post=12120"},{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_cat?post=12120"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_tag?post=12120"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}