{"id":12140,"date":"2026-11-17T21:32:59","date_gmt":"2026-11-17T18:32:59","guid":{"rendered":"https:\/\/risys.sa\/?post_type=product&#038;p=12140"},"modified":"2026-11-17T21:32:59","modified_gmt":"2026-11-17T18:32:59","slug":"apc-pdm3532iec-320-power-distribution-module","status":"publish","type":"product","link":"https:\/\/risys.sa\/en\/product\/apc-pdm3532iec-320-power-distribution-module\/","title":{"rendered":"APC PDM3532IEC-320 Three-Phase Power Module, 32 A, 320 cm"},"content":{"rendered":"<p>Rack rows rarely end at the distribution point. The second or third position in a row, or a rack across a narrow aisle, needs a feed that travels a little further than the closest unit, and the APC PDM3532IEC-320 is built for that middle distance. It carries a 400 V three-phase supply over a 320 cm output cable to one IEC 309 32 A connector, with a 32A breaker guarding the branch. Between the PDM3532IEC-260 and the PDM3532IEC-380 it sits squarely in the centre: more reach than the first, less cable to manage than the second. That balance is the reason to choose it when the measured route falls between the two, so the rack receives a protected 32 A feed without either a stretched cable or a large surplus loop behind the cabinet.<\/p>\n<h2>Inside the APC PDM3532IEC-320<\/h2>\n<h3>Supply and output<\/h3>\n<p>The module&#8217;s input is 400 V three-phase at 50 Hz. On the output side it is listed at 230 V and 400 V three-phase, which is how a low-voltage three-phase system presents itself to a load: 400 V measured between phases and 230 V from any phase to neutral. A rack PDU designed for a three-phase input takes the feed as it arrives and can spread its outlets across the phases to keep the load balanced.<\/p>\n<h3>Protection and current limit<\/h3>\n<p>Maximum line current and maximum current draw are both 32 A, and the built-in breaker is rated 32A to match. The breaker marks the boundary of the branch: when the connected rack draws more than the module is rated for, it opens before the cable or connector is pushed beyond its rating. Sizing the rack load below that figure rather than at it keeps nuisance trips away when every server in the rack powers up together after an outage.<\/p>\n<h3>Connector<\/h3>\n<p>The single outlet is an IEC 309 32 A connector, part of the industrial pin-and-sleeve family used where a plug must carry heavy current and stay seated. With one outlet, each PDM3532IEC-320 serves exactly one rack PDU, which gives every rack its own breaker and its own point of isolation.<\/p>\n<h2>Saudi deployments that suit a 320 cm feed<\/h2>\n<p>Cloud and colocation halls in Riyadh and the Eastern Province often place their three-phase distribution at the end of a row and populate outward, and the PDM3532IEC-320 suits the positions just beyond the first rack. Healthcare networks consolidating PACS and hospital information systems into central server rooms, universities running research computing clusters, and ministries moving workloads into their own data centres meet the same geometry when rooms are fitted out in phases. In telecom exchanges, where equipment racks often stand back from wall-mounted distribution, the extra reach over the PDM3532IEC-260 can save moving either the rack or the distribution point.<\/p>\n<h2>PDM3532IEC-320 compared with the rest of the family<\/h2>\n<p>Against its two closest siblings the choice is purely about route length, because the electrical profile is the same: 400 V three-phase in, 32 A, and an IEC 309 32 A connector out. Pick the PDM3532IEC-260 when the rack is close enough for a shorter cable, and the PDM3532IEC-380 when the route is longer than this model can cover. The series continues with models from the PDM3532IEC-440 to the PDM3532IEC-980, which also run on a 400 V three-phase supply, so lengths can be mixed in one room without touching the upstream design. Racks whose PDU is not built for a three-phase input need a different branch of the family, so confirm the PDU inlet before ordering.<\/p>\n<h2>Before installation<\/h2>\n<p>Prepare a 400 V three-phase upstream circuit protected for 32 A, and check the site supply frequency against the module&#8217;s 50 Hz rating. Then walk the actual cable route with a tape measure: from the distribution point, along the tray or floor void, and up inside the rack to the PDU inlet. If the total sits comfortably within 320 cm with a little slack for the bend, this is the right length. Leave the IEC 309 connector where a technician can reach it to isolate the rack, and follow the supplied installation guide when fixing the module. The PDM3532IEC-320 is grey, carries CE and VDE marks, is RoHS compliant by exemption, and is covered by a 12-month warranty.<\/p>\n<h2>Package Contents<\/h2>\n<ul>\n<li>Power distribution module<\/li>\n<li>Installation guide<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>An APC power distribution module with a 320 cm output cable that delivers a protected 400 V three-phase, 32 A branch to one rack through a single IEC 309 32 A connector.<\/p>\n","protected":false},"featured_media":21046,"comment_status":"open","ping_status":"closed","template":"","meta":{"_acf_changed":false},"product_brand":[716],"product_cat":[851],"product_tag":[],"class_list":["post-12140","product","type-product","status-publish","has-post-thumbnail","product_brand-apc","product_cat-power-distribution-pdu","first","onbackorder","sale","taxable","shipping-taxable","purchasable","product-type-simple"],"acf":[],"_links":{"self":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12140","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/comments?post=12140"}],"version-history":[{"count":1,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12140\/revisions"}],"predecessor-version":[{"id":12141,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/12140\/revisions\/12141"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media\/21046"}],"wp:attachment":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media?parent=12140"}],"wp:term":[{"taxonomy":"product_brand","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_brand?post=12140"},{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_cat?post=12140"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_tag?post=12140"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}