{"id":9412,"date":"2026-11-17T22:15:54","date_gmt":"2026-11-17T19:15:54","guid":{"rendered":"https:\/\/risys.sa\/?post_type=product&#038;p=9412"},"modified":"2026-11-18T20:57:20","modified_gmt":"2026-11-18T17:57:20","slug":"apc-e3mups80khs-three-phase-ups","status":"publish","type":"product","link":"https:\/\/risys.sa\/en\/product\/apc-e3mups80khs-three-phase-ups\/","title":{"rendered":"APC E3MUPS80KHS Three-Phase UPS, 80 kVA \/ 80 kW"},"content":{"rendered":"<p>APC E3MUPS80KHS is a three-phase UPS rated at 80 kVA \/ 80 kW, and that rating defines its place in the family: it is the frame for critical loads that have outgrown the E3MUPS60KHS but do not yet justify the E3MUPS100KHS. Because the apparent and real power ratings are the same, the whole 80 kW can be planned as usable real power for servers, control systems and building services, with no power-factor reduction to subtract from the nameplate. The unit works at 400 V in a 3:3 configuration, taking a three-phase supply in and delivering a three-phase output to the protected distribution board. Autonomy comes from an external battery system, and batteries are not included, so runtime is a decision the project makes separately, by sizing the battery cabinet against the real load and the time the site needs to bridge.<\/p>\n<h2>How the APC E3MUPS80KHS works in a facility<\/h2>\n<p>The UPS sits between the incoming three-phase feed and the critical board. While the mains or the standby generator is healthy, the load is supplied through the UPS; when the feed drops, the external battery system takes over the load until power returns or the generator comes online and settles. For an operations manager, the practical questions are therefore two: does the measured load on the critical board fit inside 80 kW with sensible headroom, and how many minutes must the batteries cover? The first question is answered by the rating of the unit. The second is answered by the battery system you pair with it, since it does not rely on a fixed internal pack whose runtime may not match your site. That leaves the designer free to match autonomy to the generator plan of each building.<\/p>\n<h2>Where an 80 kVA three-phase UPS fits in Saudi projects<\/h2>\n<p>An 80 kW protected capacity matches the critical load of a mid-sized server room in a ministry, university or bank head office, where servers, network core equipment and cooling controls share one protected board. In hospitals, it serves the IT room and the building management systems that must keep running through the transfer to generator. Industrial sites in Jubail, Yanbu and the Riyadh industrial cities can place it ahead of control rooms, SCADA servers and instrumentation panels. Commercial towers, malls and hotels use this class of UPS for the security head-end: video recording servers, access control controllers and the network that links them, so that cameras keep recording and doors keep responding through a supply interruption, within the available battery time. In every case, the three-phase output lets the protected load stay spread across the three phases instead of being forced onto one.<\/p>\n<h2>Choosing between the APC three-phase UPS models<\/h2>\n<p>Within the E3MUPS range, the E3MUPS60KHS, E3MUPS60KHBS and E3MUPS60KHB2S are rated at 60 kVA \/ 60 kW and fit loads that sit clearly below that line. The E3MUPS100KHS at 100 kVA \/ 100 kW and the E3MUPS120KHS at 120 kVA \/ 120 kW are the next steps up, while the E3MUPS200KHS at 200 kVA \/ 200 kW serves the largest critical boards in the family. Choose the E3MUPS80KHS when your measured load plus planned growth exceeds what the E3MUPS60KHS covers but stays clearly inside 80 kW; buying a larger frame for a load that will never grow into it ties up budget and floor space for no return. For much smaller three-phase loads, the E3SUPS models cover a range that starts with the E3SUPS10KHB at 10 kVA \/ 10 kW and reaches the E3SUPS40KHB at 40 kW\/40 kVA.<\/p>\n<h2>Deployment notes<\/h2>\n<p>Plan the electrical work around a 400 V three-phase supply for both input and output, and have the electrical contractor size the upstream protection and feeder cables for an 80 kVA unit. Order the external battery system together with the UPS, because batteries are not included and the battery cabinet, its cabling and its location belong in the same installation plan. The box contains a dust filter and the installation guide: use the filter from first start-up, since airborne dust is a constant in many Saudi plant rooms and warehouses, and follow the guide for the installation sequence. Keep a load register for the critical board so that new equipment is checked against the 80 kW rating before it is connected, rather than discovered as an overload at the next outage.<\/p>\n<h2>Package Contents<\/h2>\n<ul>\n<li>Dust filter<\/li>\n<li>Installation guide<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>An 80 kVA \/ 80 kW three-phase UPS from APC for 400 V 3:3 installations, working with an external battery system (batteries not included).<\/p>\n","protected":false},"featured_media":21368,"comment_status":"open","ping_status":"closed","template":"","meta":{"_acf_changed":false},"product_brand":[716],"product_cat":[845,706],"product_tag":[],"class_list":["post-9412","product","type-product","status-publish","has-post-thumbnail","product_brand-apc","product_cat-three-phase-ups","product_cat-ups-backup-power","first","onbackorder","sale","taxable","shipping-taxable","purchasable","product-type-simple"],"acf":[],"_links":{"self":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/9412","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/comments?post=9412"}],"version-history":[{"count":1,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/9412\/revisions"}],"predecessor-version":[{"id":9413,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product\/9412\/revisions\/9413"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media\/21368"}],"wp:attachment":[{"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/media?parent=9412"}],"wp:term":[{"taxonomy":"product_brand","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_brand?post=9412"},{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_cat?post=9412"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/risys.sa\/en\/wp-json\/wp\/v2\/product_tag?post=9412"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}