APC AP7920B Switched Rack PDU, 1U, 8 C13 Outlets, C14 Input
A 1U APC switched rack PDU rated 10 A at 230 V (12 A at 208 V), with eight C13 outlets and a C14 input plug that connects straight to a UPS outlet.
Original price was: 2,930.47 SAR.2,754.64 SARCurrent price is: 2,754.64 SAR. excl. VAT
Available on backorder
RISYS can programme and prepare devices before delivery. Contact us for quantity and project details.
Wholesale and project supply — up to 45% off











Up to 45% off wholesale supply.
Overview
The APC AP7920B is a switched rack power distribution unit built around a modest, clearly defined load: it is rated 10 A at 230 V or 12 A at 208 V, and that current rating is what separates it from the heavier models in the same APC family. In a single rack unit it carries eight IEC C13 outlets and draws its power through one cord ending in an IEC 60320 C14 plug. The plug matters more than it first appears. It means the APC AP7920B connects directly to a C13 outlet on a UPS, so a whole cabinet of network equipment can sit behind battery backup without an electrician installing a new socket. Its total capacity is 2300 VA, a budget that suits a communications cabinet of switches, a firewall, a router and a video recorder, provided their combined draw stays inside it. It accepts any supply within 200–240 V at 50/60 Hz.
What the APC AP7920B does in a working rack
A rack PDU replaces the loose power strips that tend to collect at the back of a cabinet. The AP7920B mounts horizontally in one 1U position using the rack mounting brackets supplied in the box, so the outlets stay in a fixed place instead of hanging from cable ties. Because it takes only 1U, the remaining rack positions stay free for active equipment, which counts in small cabinets where every unit of height is already allocated.
Every outlet is an IEC C13, the receptacle that accepts the standard C14-ended cords shipped with most servers, switches, NVRs and firewalls. That keeps the cabinet free of adaptors and domestic plugs, and it means a device can be moved from one rack to another without changing its power cord.
The unit passes its input through to the outlets: on a 230 V supply the eight outlets deliver 230 V, and on a 208 V supply they deliver 208 V. That is why APC publishes two ratings. On a 230 V circuit, plan the rack against 10 A and 2300 VA. Where a room is wired for 208 V, the unit carries up to 12 A.
The single input cord is 1.98 m (6.5 ft) long. That reach suits a UPS installed at the bottom of the same rack or standing directly beside it. If the UPS sits further away, decide where the PDU will sit in the rack before fixing the brackets, so the cord reaches without strain.
Where it fits in Saudi facilities
The AP7920B is at home in the small and mid-sized rooms that make up most installed IT across the Kingdom: the communications cabinet in a bank branch, the IT room of a private school, the network rack in a clinic or a pharmacy chain, and the server corner of a regional office. In each of these, one UPS feeds one rack, and plugging the PDU into that UPS is the cleanest way to bring every device under battery protection.
Security integrators will recognise the pattern from CCTV projects. A control room in a residential compound, a warehouse or a school usually runs PoE switches, one or two NVRs, a video wall controller and a firewall from a shared rack. Eight C13 outlets cover that equipment list, and the 2300 VA ceiling is a useful planning figure as the camera count, and with it the PoE switch load, grows over the life of the project.
Retail and hospitality operators with a small network cabinet in every branch benefit from the same arrangement: one standard model rolled out across all branches, plugged into each branch UPS, with no site-specific electrical works.
Choosing between the AP7920B, AP7921B and AP7922B
The three switched models in this family do the same job and are separated mainly by how much current they handle. The AP7921B keeps the 1U height and eight C13 outlets but moves up to 16 A, rated 3.7 kW at 230 V, and its plug changes to an IEC C20, which needs a C19 receptacle rather than the common C13 outlet. The AP7922B goes further, to 32 A at 230 V, occupies 2U, carries sixteen C13 outlets and uses an IEC 60309 industrial plug that requires its own dedicated socket.
Choose the AP7920B when the real load of the rack fits within 2300 VA and you want to plug the PDU into an existing UPS outlet. Step up to the AP7921B when the cabinet holds more servers or storage and its draw approaches the AP7920B ceiling, and to the AP7922B for dense racks fed from a dedicated circuit. Picking the smallest unit that comfortably carries the load keeps the input connection simple; picking one that already runs near its limit leaves no room to grow.
Deployment notes
Before installation, confirm that the UPS has a free C13 outlet and that its own output rating covers the full load you intend to connect, because the PDU can never deliver more than the outlet feeding it. Add up the nameplate ratings of every device that will plug into the eight outlets and compare the total with 2300 VA on a 230 V supply, leaving a margin for equipment added later.
For equipment with dual power supplies, the usual practice is to install two AP7920B units on separate feeds so each device draws from both; losing one feed or one UPS then leaves the equipment running. The unit runs on 50/60 Hz supplies alike, and the box contains the rack mounting brackets, an installation guide and a user manual.
Package Contents
- Installation guide
- Rack mounting brackets
- User manual
Technical Specifications
- Brand
- APC
- Model
- AP7920B
- Mounting
- 1U
- Ports
- input: 1 IEC 60320 C14 power input; output: 8 IEC 60320 C13 outlets
Frequently Asked Questions
Can the APC AP7920B plug directly into a UPS?
Yes. Its input cord ends in an IEC 60320 C14 plug, which fits a C13 outlet on a UPS. The UPS outlet and the UPS itself must be rated for the full load connected to the PDU.
What is the maximum load of the AP7920B?
It is rated 10 A at 230 V, a load capacity of 2300 VA, or 12 A when it runs on a 208 V supply.
How many outlets does it have, and of what type?
Eight IEC C13 outlets, which accept the standard C14-ended power cords used by most servers, switches and recorders.
How much rack space does it take?
One rack unit (1U). It mounts horizontally with the rack mounting brackets included in the box.
Which supply voltages does it accept?
Nominal input is 200/208/230 V, with an acceptable range of 200–240 V at 50/60 Hz. The outlets deliver 208 or 230 V, matching the supply.

APC UPS systems keep servers and network cabinets running through outages and unstable mains, and the wider APC range extends into the racks, power distribution and sensors around them. APC began in the United States as American Power Conversion and
Browse brand productsDelivery across Saudi Arabia
Clear warranty
Some devices or frequencies may require a permit or approval depending on the intended use and the regulations in force in the Kingdom. Requirements are clarified before project orders are fulfilled.
Customer Reviews
No ratings yet for this product
Only logged in customers who have purchased this product may leave a review.
Related Products
APC APDU9959EU3 Switched Rack PDU, 16A 230V, IEC309 Cord
On backorder
APC AP8653 Metered-by-Outlet Switched Rack PDU 32A
On backorder
APC EPDU1116S Switched Rack PDU 16A, 20 C13 and 4 C19
On backorder
APC PDM3516IEC-500 Power Distribution Module, 16A, 500 cm
On backorder





Reviews
There are no reviews yet.